Page 1DIRECT VENT, ZERO CLEARANCEGAS FIREPLACE HEATERMILLIVOLT STANDING PILOTDVP(42,48)FP3(0,1,2,3)(N,P)-4DIRECT IGNITIONDVP(42,48)FP5(0,1,2,3)N-1INTE
31455-8-0415Page 10CLEARANCESClearance to CombustiblesBack 0" (0 mm)Side 0" (0 mm)Floor 0" (0 mm)Top Stand-off 0" (0 mm)Top Framin
31455-8-0415 Page 11Figure 7NOTICE: Island and Room Divider installation is possible as long as the horizontal portion of the vent system does not ex
31455-8-0415Page 12GAS SUPPLYThe gas pipeline can be brought in through the right or left side of the appliance. Consult the current National Fuel Gas
31455-8-0415 Page 13INSTALLATIONFraming and Finishing 1. Choose unit location.2. Frame in replace with a header across the top. It is important to
31455-8-0415Page 14INSTALLATIONFlush Mount Mantel InstallationThe replace must extend 3/4” beyond nished wall surface when using a ush mount mantel
31455-8-0415 Page 15INSTALLATIONFlush Wall InstallationFigure 15Combustible Surround InstallationFigure 16Note: For mantelshelf requirements, see Figu
31455-8-0415Page 16INSTALLATIONREAR ONLY, STRAIGHT OUT THE BACK"A" "B" MODEL 6"(152mm) 5 1/8"(130mm) to 6 /2"(165mm
31455-8-0415 Page 17To Use the Vent Graph1. Determine the height of the center of the horizontal vent pipe. Using this dimension on the Sidewall Vent
31455-8-0415Page 18VENTING FIREPLACE - TOPBelow Grade InstallationWhen it is not possible to meet the required vent terminal clearances of 12” (305mm)
31455-8-0415 Page 19Figure 26MINIMUM HOLE LOCATION DIMENSIONS FOR THROUGH THE WALL HORIZONTAL INSTALLATIONS WITH 90 DEGREE ELBOW OFF TOP OF FIREPLACEF
31455-8-0415Page 2TABLE OF CONTENTSIMPORTANT SAFETY INFORMATION ...
31455-8-0415Page 20Figure 29Figure 30Figure 31EXAMPLES - TOP VENT RUN
31455-8-0415 Page 21VENTING EXAMPLES WHEN USING DVA47 ADAPTORVertically Off Top of Fireplace OnlyExampleH1 = 2ftV1 = 20ftH = 2ft V = 20ftDVA47 ADAPTO
31455-8-0415Page 22 Acceptable vertical and horizontal vent run. Unacceptable vertical and horizontal vent run.Figure 35Venting Graph (Dimensions in
31455-8-0415 Page 23Figure 36Figure 37Figure 38Figure 39Model Maximum Pipe Length H1DVP42 24"DVP48 24"Model Maximum Pipe Length H1DVP42 24&q
31455-8-0415Page 24REAR VENT CONVERSIONConverting ue take-off to rear ventingWhen switching out the ue and inlet vent collars to run horizontally of
31455-8-0415 Page 25Figure 41A = *Clearance above grade, veranda, porch, deck or balcony [*12 inches (30cm) minimum]B = clearance to window or do
31455-8-0415Page 268" VENTING FRAMING AND FINISHINGInstalling Support BracketsA horizontal pipe support MUST BE used for each 3 feet of horizonta
31455-8-0415 Page 278" VENTING FRAMING AND FINISHING (continued)Figure 44Figure 45Figure 46See Horizontal Termination Page 31 and Vertical Termin
31455-8-0415Page 286 ⅝" VENTING FRAMING AND FINISHINGInstalling Support BracketsA horizontal pipe support MUST BE used for each 3 feet of horizon
31455-8-0415 Page 296 ⅝" VENTING FRAMING AND FINISHING (continued)Figure 50Figure 51See Horizontal Termination Page 31 and Vertical Termination o
31455-8-0415 Page 3DO NOT OPERATE THIS APPLIANCE WITHOUT GLASS FRONT PANEL INSTALLEDBefore enclosing the vent pipe assembly, operate the appliance to
31455-8-0415Page 30Termination clearance for buildings with combustible and noncombustible exteriors.Vertical Sidewall InstallationsImportant! Minimum
31455-8-0415 Page 31NOTE: Termination cap should pass through the wall restop from the exterior of the building. Adjust the termination cap to its
31455-8-0415Page 32VERTICAL TERMINATIONLocate and mark the center point of the venting pipe. Using a nail on the underside of the roof and drive this
31455-8-0415 Page 33VERTICAL TERMINATIONInstalling the Vent System in a ChaseA chase is a vertical box-like structure built to enclose the
31455-8-0415Page 34NOTICE: For top vent installation only: Use of a DVA47 adap-tor is required.CAUTION: Sharp edges, use protective gloves when insta
31455-8-0415 Page 35DVVK-4RE VENT KIT INSTALLATION INSTRUCTIONSFigure 60Figure 617. Remove outside mounting plate with tube attached from wall. Mark
31455-8-0415Page 36Follow correct option according to venting method.Connecting Directly to FireplaceIf the air inlet and ue outlet tubes are to be c
31455-8-0415 Page 37DVVK-5F FLEX VENT INSTRUCTIONSThe DVVK-5F FLEX VENT KIT includes the following compo-nents:• (1) Horizontal Termination Cap• (
31455-8-0415Page 38Model AIR SHUTTER SETTINGSBURNER ORIFICEOpening "A" Propane/LP OriceDVP42 Full Open #52DVP48 Full Open #51Maxitrol Valve
31455-8-0415 Page 39LOG PLACEMENT (4 LOG SET)Before you begin: If you are installing logs into the DVP42 or DVP48 model then this replace is supplied
31455-8-0415Page 4Some people cannot smell well. Some people cannot smell the odor of the chemical put into the gas. You must nd out if you can smell
31455-8-0415Page 40The OWNER should carefully read and follow these operating instructions at all times. Lower the door assembly to view the g
31455-8-0415 Page 41STANDING PILOT OPERATING INSTRUCTIONS Remote/Off/On SwitchThe replace is equipped with a Remote/OFF/ON switch. A wire harness is
31455-8-0415Page 42Figure 75MILLIVOLT SYSTEM STANDING PILOT WIRING DIAGRAM
31455-8-0415 Page 431. Stop! Read the safety information above.2. Set REMOTE/OFF/ON switch to OFF.3. Turn off all electric power to the appliance
31455-8-0415Page 44With proper installation and maintenance, your new Direct Vent Gas Fireplace will provide years of trouble-free service. If you do
31455-8-0415 Page 45A. BEFORE LIGHTING smell all around the appliance area for gas. Be sure to smell next to the oor because some gas is heavier tha
31455-8-0415Page 46LED CODESSteady ON Normal operation, power ON to control2 Flashes 3 unsuccessful ignition trials3 Flashes Main burner ame failed 4
31455-8-0415 Page 471. Remove glass door and place away from the replace.2. Turn on gas shut off valve. Follow ignition procedure.3. If burner doe
31455-8-0415Page 48The conversion shall be carried out in accordance with the requirements of the provincial authorities having jurisdiction and in ac
31455-8-0415 Page 49IPI ELECTRONIC SYSTEM OPERATING INSTRUCTIONS5.25 VDC ELECTRONIC CONTROL VALVEThe electronic control valve system includes the abil
31455-8-0415 Page 5REQUIREMENTS FOR MASSACHUSETTSFor all side wall horizontally vented gas fueled equipment installed in every dwelling, building or s
31455-8-0415Page 50IPI ELECTRONIC SYSTEM WIRING DIAGRAMIf any of the original wire as supplied with this unit must be replaced, it must be replaced wi
31455-8-0415 Page 51TO TURN OFF GAS TO FIREPLACEGAS COCK1. STOP! Read the safety information above.2. Turn OFF electric power to the appliance.3. R
31455-8-0415Page 52Brief Description of the ComponentsThe gas valve is tted with a manual HI/LO knob to allow for man-ual modulation of the gas outle
31455-8-0415 Page 531If the DFC giving signal lock out:The board should be unlocked toreinitiate a pilot flame ignition (forthe correct unlock sequenc
31455-8-0415Page 54INTERMITTENT PILOT CONTROL SYSTEM TROUBLESHOOTING
31455-8-0415 Page 55RF VALVE OPERATION (AF-4040 Electronic Gas Valve system only)Please refer to the separate instructions for detailed operation and
31455-8-0415Page 56MAINTENANCEMaintenance frequency must be determined individually for each application. Some considerations are:• Exposure to water
31455-8-0415 Page 57Figure 79RF WIRING DIAGRAMNote: For "RF" Fireplace models with Premium Multi-Function Remote Control, Refer to the sepa
31455-8-0415Page 58FOR YOUR SAFETY READ BEFORE LIGHTINGWARNING: IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION MAY RESULT CAUSIN
31455-8-0415 Page 59MAINTENANCE AND SERVICEPlease NoteIt is normal for appliances fabricated of steel to give off some expansion and/or contraction no
31455-8-0415Page 6Instructions to Installer1. Installer must leave instruction manual with owner after installation.2. Installer must have ow
31455-8-0415Page 60DVP42FP(3,5,7,9) PARTS LISTIndex No.Part NumberDescriptionDVP42FP3 DVP42FP5 DVP42FP7 DVP42FP91 R7654 R7654 R7654 R7654 Insulation,
31455-8-0415 Page 61DVP42FP(3,5,7,9) PARTS LIST41 R3436 - R2522 - Remote/On/Off Switch43 - R7615 - Cord Set44 - R8144 - - Wire Harness (DI)45 - - R111
31455-8-0415Page 62DVP48FP(3,5,7,9) PARTS LISTIndex No.Part NumberDescriptionDVP48FP3 DVP48FP5 DVP48FP7 DVP48FP91 R7654 R7654 R7654 R7654 Insulation,
31455-8-0415 Page 63 Use Only Manufacturer’s Replacement Parts. Use of Any Other Parts Could Cause Injury Or Death.DVP48FP(3,5,7,9) PARTS LIST44 - R81
31455-8-0415Page 64PARTS VIEW
31455-8-0415 Page 65To Order Parts Under Warranty, please contact your local Empire dealer. See the dealer locator at www.empirecomfort.com. To provid
31455-8-0415Page 66Attention: Install blower assembly before connecting gas inlet supply lineNote: Junction box on right side of replace must be p
31455-8-0415 Page 671 R7731 BLOWER MOTOR2 31920 SWITCH ASSEMBLY3 R4192 SPEED CONTROL KNOB4 R4186 SPEED CONTROLFBB4 OPTIONAL VARIABLE SPEED BLOWER INST
31455-8-0415Page 681. Using gloves, unpack liner components and check for damaged or missing components.2. Lower bottom louver and remove upp
31455-8-0415 Page 69The following accessory parts can be obtained from your Empire Comfort Systems dealer. If you need additional information beyond w
31455-8-0415 Page 7Remote Control Options & AccessoriesDescriptionFRBC Millivolt/IP Battery Remote ON/OFFFRBTC Millivolt/IP Battery Remote T-StatT
31455-8-0415Page 70Web Site www.empirecomfort.comEmpire Comfort Systems918 Freeburg AvenueBelleville, Illinois 62220-2623CLEARANCES TO COMBUSTIBLESGA
31455-8-0415 Page 71Web Site www.empirecomfort.comEmpire Comfort Systems918 Freeburg AvenueBelleville, Illinois 62220-2623FRAMING DIMENSIONFIREBOX DI
31455-8-0415Page 72WARRANTYEmpire Comfort Systems Inc. warranties this hearth product to be free from defects at the time of purchase and for the peri
31455-8-0415Page 8VENT SYSTEM IDENTIFICATIONFigure 1Begin the vent system installation by selecting the type of venting to be installed and the path t
31455-8-0415 Page 9The following vent systems are acceptable for use with the DVP (42,48) series replaces:Simpson Duravent® GS 5" - 8&